Growatt SPF 5000 ES parameter table

find below a tabel with the parameters you can set in the Growatt SPF inverters.

Column B is meant to be the menu where you can access this parameter. In some cases for 111 and 305 you have to hold arrow up and down at the same time in the inverter and press the menu number as password. There are some descriptions for now in german but I will update the list in the future.

Parameter 25, 26 and 35 are not used or unknown for now. If you have further details for those parameters please report…

ProgramMenuDescription
1000Output source priority: To configure load power source priority
2000Maximum charging current:
set total charging current for
solar and utility chargers.
(Max. charging current =
utility charging current +
solar charging current)
3000AC input voltage range
4000Power saving mode
enable/disable
5000Battery type
6000Auto restart when overload
occurs
7000Auto restart when over
temperature occurs
8000Output voltage
*This setting is only
available when the inverter
is in standby mode (Switch
off).
9000Output frequency
*This setting is only
available when the inverter
is in standby mode (Switch
off).
10000Number of series
batteries connected
11000Maximum utility charging
current
Note: If setting value in
Program 02 is smaller
than that in Program 11,
the inverter will apply
charging current from
Program 02 for utility
charger
12000Setting voltage point back
to utility source when
selecting “SBU priority” or
“Solar first” in program 01
13000Setting voltage point back
to battery mode when
selecting “SBU priority”
or “Solar first” in program
01
14000Charger source priority:
To configure charger
source priority
15000Alarm control
16000Backlight control
17000Beeps while primary
source is interrupted
18000Overload bypass:
When enabled, the unit
will transfer to line mode
if overload occurs in
battery mode.
19000C.V. charging voltage.
If self-defined is selected
In program 5, this
program can be set up
20000Floating charging voltage.
If self-defined is selected in
program 5, this program
can be set up
21000Low DC cut-off voltage.
If self-defined is selected in
program 5, this program can
be set up.
Low DC cut-off voltage will
be fixed to setting value no
matter what percentage of
load is connected.
22inactiveSolar Balance SbE enabled (max charge plus loads) / Sbd disabled (max charge only)
23000AC output mode
*This setting is only
available when the inverter
is in standby mode (Switch
off).
Note: Parallel operation
can only work when battery
connected
24inactiveNEC disable/enable closes dry contact on battery /opens relay on utility
25
26
27111CAP (Inverter Capacity)
28000Address setting
(for expansion)
29111Grdv (vermutlich Grid Voltage)Offsetwert um die Netzspannung zu kalibrieren
30111bat.v (Battery Voltage Offset)braucht man wenn die Bat V im Lastzustand bei mehreren parallelen Geräten unterschiedlich ist hab ich probiert und tut genau das was ich beschreibe…
31111INv (vermutlich Invertervoltage Offset)(vermutlich Invertervoltage Offset)
32111OUtv (Output Voltage Offset)vermutlich auch ein Offsetwert für die abgebene AC Spannung
33111Pvv (PV Voltage)vermutlich auch ein offsetwert für den PV Spannungseingang
34305RST parameter reset
35
36LI- P5Battery Protocoll CAN/RS485
37000Real time setting—Year
38000Real time setting—Month
39000Real time setting—Date
40000Real time setting—Hour
41000Real time setting—Minute
42000Real time setting—Second
43000Battery equalization
44000Battery equalization
voltage
45000Battery equalized time
46000Battery equalized timeout
47000Equalization interval
48000Equalization activated
immediately
49000Utility charging time
50000AC output time
51111FrSt dis???
52111PvIS dis???
53111EtL???